20 3 35 kV XLPE INSULATED THREE CORE CABLES WITH COPPER CONDUCTOR
YXC8V-R (20.3/35 kV)

20 3 35 kV XLPE INSULATED THREE CORE CABLES WITH COPPER CONDUCTOR
YXC8V-R (20.3/35 kV)

Share:
YXC8V-R 20.3/35 kV TSEK

N2XSEY 20.3/35 kV

Structure

  1. Stranded copper conductor
  2. Inner semi condutive layer
  3. XPLE insulation
  4. Outer semi conductive layer
  5. Semi conductive tape
  6. Copper wire screen
  7. Filler
  8. PVC outer sheath
Technıcal Data

Maximum operating temp.:90°C

Max.short circuit temp.:250°C (+≥ 5 sn)

Installation temp.min:-5 °C

Standarts: TS IEC 60502-2 VDE 0276

Applıcatıons

They are used in cable ducts, outdoor and indoor installations, under ground where the short circuit levels are high and industrial areas fed by electrical also These cables use where there is risk of mechanical damage.

Description

Teknik Özellikler / Technical Features

Normal Kesit

Kablo Dış Çapı

Akım Taşıma Kapasitesi

Çalışma İndüktansı

Çalışma Kapasitesi

İletken DC Direnci (20 oC)

Net Ağırlık

Sevk Uzunluğu

Rated Cross Section

Overall Diameter Of Cable

Current Carrying Capacity

Operating Inductance

Operating Capacity

Conductor DC Resistance at (20 oC)

Net Weight

Delivery Length

mm2

mm

Air (A)

Ground (A)

mH / Km

µF / km

Ohm / Km

Kg / Km

Mt

3×35/16

72.50

182

183

0,48

0,10

0,524

6380

500

3×50/16

75.00

217

214

0,45

0,11

0,387

7080

250

3×70/16

78.50

269

261

0,42

0,12

0,268

8170

250

3×95/16

82.50

326

313

0,41

0,14

0,193

9380

250

3×120/16

86.50

377

356

0,39

0,15

0,153

10630

250

3×150/25

89.00

426

400

0,37

0,16

0,124

11880

250

3×185/25

93.50

488

441

0,36

0,17

0,0991

13660

200

3×240/25

98.50

576

510

0,34

0,18

0,0754

15980

200

3×300/25

104.50

654

604

0,33

0,20

0,0601

18590

200

3×400/35

111.00

754

688

0,31

0,24

0,0470

22240

200

Translate »